ROSEMOUNT 644 Temperature Transmitter

: In stock

: Temperature Meaurement

: ROSEMOUNT

Regular price Sale

Overview Rosemount™ 644 Temperature Transmitter Engineered for versatility, the Rosemount 644 Temperature Transmitter is available with HART™, FOUNDATION™ Fieldbus or PROFIBUS™ protocols in head, field or rail mount...

Overview

Rosemount™ 644 Temperature Transmitter
Engineered for versatility, the Rosemount 644 Temperature Transmitter is available with HART™, FOUNDATION™ Fieldbus or PROFIBUS™ protocols in head, field or rail mount styles and a variety of enclosure options. By adding a Local Operator Interface (LOI), you
can update your transmitter configuration in the field without tools. For diverse application requirements, this transmitter
includes diagnostic capabilities, such as Hot Backup™ capability, sensor drift alert and thermocouple degradation.

Features

 * Extremely versatile temperature transmitter available in HART™, FOUNDATION™ Fieldbus or PROFIBUS™ protocols
* Diverse mounting configurations including head, field or rail mount with many enclosure options
* LOI option eliminates the need for special configuration tools (i.e. field communicator) for ease-of-use
* Transmitter-sensor matching with Callendar-Van Dusen constants reduces total measurement error
* Hot Backup™ capability and sensor drift alert with dual sensors ensure measurement integrity
* Thermocouple degradation diagnostic monitors thermocouple health to detect degradation before failure
* Minimum and maximum temperature tracking observes temperature extremes for easy troubleshooting
* Device dashboards provide easy interface for simplified device configuration and diagnostic troubleshooting

Specification

item
value
Warranty
1 Year
Customized support
OEM, ODM, OBM
Place of Origin
United States
Brand Name
EMERSON/ROSEMOUNT
Model Number
644 Temperature Transmitter
Environmental conditions

Ambient operating temperature range
Standard: -50 to +85 °C SIL: -40 to +80 °C
Storage temperature
-50 to +85 °C
Calibration temperature
23...25 °C
Humidity
< 99% RH (non-cond.)
Protection degree
IP20
Mechanical specifications

Dimensions (H x W x D)
109 x 23.5 x 104 mm
Weight, single input / dual input
150 g/160 g
Maximum wire size
0.13...2.08 mm2 /AWG 26...14 stranded wire
Screw terminal torque
0.5 Nm
Vibration: IEC 60068-2-6
 2...25 Hz: ±1.6 mm ■ 25...100 Hz: ±4 g
Common specifications

Supply voltage, DC
Rosemount 644R Ordinary Location: 7.5(1)...48(2)VDC ■ Rosemount 644R Hazardous Approval: 7.5(1)...30(2)VDC
Additional minimum supply voltage when using test terminals
0.8 V
Maximum internal power dissipation
≤ 850 mW per channel
Minimum load resistance at > 37 V supply
(Supply voltage – 37)/23 mA
Isolation voltage, test/operation
Rosemount 644R Ordinary Location: 2.5 kVAC/55 VAC ■ Rosemount 644R Hazardous Approval: 2.5 kVAC/42 VAC
Polarity protection
All inputs and outputs
Write protection
Jumper or software
Warm-up time
< 5 minutes
Start-up time
< 2.75 seconds
Programming
HART® protocol
Signal/noise ratio
> 60 dB
Long-term stability, better than
±0.05% of span/year ■ ±0.18% of span/5 years
Response time
70 ms
Programmable damping
0-60 s
Signal dynamics, input
24 bit
Signal dynamics, output
18 bit
Effect of supply voltage variation
< 0.005% of span/VDC
Accuracy example
When using a Pt 100 (α = 0.00385) sensor input with a 0-100 °C span: ■ Digital accuracy = ± 0.15 °C ■ D/A accuracy = ± 0.03% of
100 °C or ± 0.03 °C ■ Total accuracy = ± 0.18 °C





please contact email for more about the shipping cost

We normally ship by DHL, UPS, FEDEX or TNT,

some country could not be ship by above method, then we would use EMS or Country Logistics line.