Endress+Hauser Ultrasonic Measurement Time-of-Flight Prosonic FMU95

: В наличии

: Level Measurement

: Endress+Hauser

Обычная цена Распродажа

Overview Transmitter in housing for field or top hat rail mounting for up to 10 sensors FDU90/91/92/93/95 Specs at a glance * Accuracy+/- 2mm + 0.17% of measured...

Overview

Transmitter in housing for field or top hat rail mounting for up to 10 sensors FDU90/91/92/93/95

Specs at a glance
* Accuracy
+/- 2mm + 0.17% of measured distance

Application

Prosonic FMU95 separated version with field housing or top hat rail housing for control cabinet instrumentation are suited for continuous, non-contact level measurement of fluids, pastes, sludge and powdery to coarse bulk solids.

Continuous, non-contact level measurement of fluids, pastes, sludge and powdery to coarse bulk materials with up to 5 or 10 ultrasonic sensors.
* Measuring range up to 45m (148ft) (depending on sensor and material measured)
* Calculation of average values or sums

Benefits

* Simple, menu-guided operation with 6-line plain text display, 15 languages selectable
* Envelope curves on the display for quick and simple diagnosis
* Easy operation, diagnosis and measuring point documentation with the supplied "FieldCare" operating program
* Time-of-Flight correction via integrated or external temperature sensors
* Linearization (up to 32 points, freely configurable)
* System integration via PROFIBUS DP with up to 20 measured values
* Automatic detection of the sensors FDU9x

Specification

item
value
Grade
Industrial
Warranty
1 Year
Customized support
OEM
Place of Origin
Germany
Brand Name
endress+hauser
Model Number
Prosonic FMU95
Mode
Ultrasonic measurement Time-of-Flight
Measuring Principle
Ultrasonic
Characteristic / Application
Separated version with Field housing or top hat rail housing for control cabinet instrumentation, 5 or 10 channel version
Specialities
Protection Class IP 66 / NEMA 4x
automatic sensor recognition of FDU9x sensors
Supply / Communication
90 ... 253 VAC
10.5 ... 32 VDC
Profibus DP
Accuracy
+/- 2mm + 0.17% of measured distance
Ambient Temperature
-40 °C ... 60 °C
(-40 °F ... 140 °F)
Communication
Profibus DP
Certificates / Approvals
ATEX, CSA
Options
Illuminated display, 6 line graphic display with country specific menu guidance, on-site diagnosis with envelope curve on display